Two 60Hz alternators are driven by shunt motors. The shunt motors have speed-load droop characteristics of 3% and 4% respectively. The alternators are in parallel and each carrying 50 kW. There is no automatic speed-load control. An additional 50 kW load is switched-on. What are the resulting loads of the alternators assuming that the speed-load control of each is not adjusted?

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter31: Three-phase Alternators
Section: Chapter Questions
Problem 1RQ: What conditions must be met before two alternators can be paralleled together?
icon
Related questions
Question

Two 60Hz alternators are driven by shunt motors. The shunt motors have speed-load droop characteristics of 3% and 4% respectively. The alternators are in parallel and each carrying 50 kW. There is no automatic speed-load control. An additional 50 kW load is switched-on. What are the resulting loads of the alternators assuming that the speed-load control of each is not adjusted?

Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning